186-9497-0015
MiCOM Substation Applications

MiCOM Substation / Feeder Applications

The MiCOM range of relays offers varying levels of functionality and hardware options to best suit the protection requirements and allows the customer to choose the most cost effective solution for their application.

The versatile hardware allows for application in many installations and a common relay management software (MiCOM S1 Studio) makes for easy configuration and application.

Basic Feeder Protection Relays — MiCOM 10 Series

The 10 series hardware platforms are the building blocks of the MiCOM protection relay range providing the capability for a wide variety of protection, control, measurement, monitoring and communication functions.

The MiCOM P11x relays are suitable for all the applications where overcurrent and/or ground fault protection are required. P11x can be applied to medium and low voltage electrical systems as an optimized and cost-efficient solution tailored to user’s needs.

Standard and Advanced Feeder Protection Relays — MiCOM 30 and 40 Series

  • Easergy MiCOM P132 offers a flexible and powerful feeder management device housed in a 4U case in 24TE, 40TE or 84TE widths. Easergy MiCOM P132 offers bay control for up to 3 devices and a library of 80 pre-engineered templates to reduce engineering time.

  • Easergy MiCOM P139 one-box solution is the most advanced in the range. It’s available in 40TE or 84TE width, 4U case sizes. It offers bay control for up to 10 devices. It uses a pre-engineered library of up to 300 templates for efficient engineering and commissioning.

  • Easergy MiCOM P14x Feeder Management and Overcurrent Protective Relays are especially suitable where a complete or advanced power system protection scheme solution is required.

The following models are available:

  • Easergy MiCOM P141 – Feeder management relay

  • Easergy MiCOM P142 – Feeder management with integrated Autoreclose

  • Easergy MiCOM P143 – Feeder management, integrated Autoreclose and Check Synchronism

  • Easergy MiCOM P145 – Feeder management, Autoreclose, Check Synchronism and Enhanced operator control functions


Functions of Feeder Management Relays

ANSI

Protection Function

P111

P115

P116

P132

P139

P141

P142

P143

P145

25

Check synchronizing

   

●

●

  

●

●

32

Directional power

   

●

●

●

●

●

●

32V

Voltage controlled direct. reactive power

   

●

●

    

34

Master sequence device

    

●

    

37

Undercurrent

  

●

●

●

●

●

●

●

46

Negative sequence overcurrent

  

●

●

●

●

●

●

●

46BC

Broken conductor

  

●

●

●

●

●

●

●

47

Negative sequence over voltage

   

●

●

●

●

●

●

48

Incomplete sequence relay

   

●

●

    

49

Thermal overload

●

 

●

●

●

●

●

●

●

50/51N

Ground fault

●

●

●

●

●

●

●

●

●

50/51P

3 Phase overcurrent

●

●

●

●

●

●

●

●

●

50/51P/N

1 Phase or ground overcurrent

   

●

●

    

50BF

Circuit breaker failure

●

●

●

●

●

●

●

●

●

51LR

Motor

   

●

●

    

51V

Voltage controlled overcurrent

   

●

●

●

●

●

●

59/27

Over / Under voltage

   

●

●

●

●

●

●

59N

Residual over voltage

   

●

●

●

●

●

●

64

Restricted ground fault

   

●

●

●

●

●

●

66

Startup monitoring

   

●

●

    

67N

Ground fault directional

   

●

●

●

●

●

●

67N

Transient ground fault detection

   

●

●

    

67N

Sensitive directional ground fault

   

●

●

●

●

●

●

67P

Phase directional

   

●

●

●

●

●

●

67W

Wattmetric ground fault

   

●

●

●

●

●

●

79

Autoreclose

  

●

●

●

 

●

●

●

81

Under / Over frequency

   

●

●

●

●

●

●

81P

Under frequency load shedding

   

●

●

    

81R

Rate of change of frequency

   

●

●

●

●

●

●

85

Protective signaling

   

●

●

    

86

Lock-out

●

●

●

●

●

●

●

●

●

CTS

Current transformer supervision

   

●

●

●

●

●

●

SOTF

Switch on to fault

●

 

●

●

●

●

●

●

●

TCS

Trip circuit supervision

●

 

●

●

●

●

●

●

●

VTS

Voltage transformer supervision

   

●

●

●

●

●

●

YN

Neutral admittance

   

●

●

●

●

●

●

 

Circuit breaker monitoring

●

 

●

●

●

●

●

●

●

Cold load pick-up

●

 

●

●

●

●

●

●

●

Inrush blocking

●

 

●

●

●

●

●

●

●

InterMiCOM

   

●

●

●

●

●

●

Limit value monitoring

   

●

●

    

Typical Catalog Numbers

Catalog Numbers

Description

Standard

P14121RABM0B48L

Series 40 - Substation/Feeder Protection, P141 (48-110Vdc), 1/5A CT inputs, 8In/7Out (user configurable voltage thresholds), 3xRJ-45, IEC61850, DNP3

Advanced

P14521RHBM0B48M

Series 40 - Substation/Feeder Protection, P141 (48-110Vdc), 1/5A CT inputs, 16In/20Out (user configurable voltage thresholds), 4 high break outputs, 3xRJ-45, IEC61850, DNP3

  Tel

  18694970015

  Email

  sales@njzndq.com 

     WeChat 

   

WeChat QR code
Nanjing Zhuneng Electric Co., Ltd

Mobile number: 18694970015

WeChat: power1411913

Email: sales@njzndq.com

Address: Building 16, Liandong U Valley Industrial Park, No.24 XuefuRoad, Jiangbei New District, Nanjing, Jiangsu, China

Copyright © 2024 Guodian Nanjing Automation Co., Ltd. All rights reserved.
Contact
Navigation
WhatsApp
Follow Us:
Powerby Feedback Follow Data